ETHERNET GATEWAY
POWER ELECTRONICS
22
INSTALLATION AND CONNECTION
Once the device is connected, set the following parameters as
follows:
Parameter
Description
Setting
drv
Drive mode
3
RS485 communication.
Frq
Frequency setting
mode
7
RS485 communication.
I60
Slave No. in
communication net
1 – 250 Use different numbers in case of more than 1 inverter
are installed.
I61
Transmission speed
in communication net
3
3: 9.600bps; default
I59
Selection of
communication
protocol
0
0: Modbus RTU
I65
Parity/Stop bit setting
3
Parity: Odd, Bit Stop: 1
Connection diagram:
Figure 3.8 SD250
– Ethernet Gateway connection