ETHERNET GATEWAY
POWER ELECTRONICS
16
INSTALLATION AND CONNECTION
CONNECTOR
or
LED
FUNCTION
DESCRIPTION
J200
Power supply connector
Brings 24Vdc power supply to the device
PIN
SIGNAL
1
GND
2
+24VDC
3
EARTH
J401
RS485 connector
Used for MODBUS-RTU connection
PIN
SIGNAL
1
RS485 A
2
RS485 B
3
GND
J302
USB connector
Used for configuration and updates of software
J500
RJ45 connector
Used for Ethernet connection
LED10
Gateway status
COLOUR: GREEN
BLINKING WITH 200ms INTERVAL: the gateway is
in configuration mode
BLINKING WITH 1s INTERVAL: the gateway is in
operation mode
OFF: the gateway is not processing code
LED100
MODBUS RTU status
GREEN: MODBUS RTU communication success
RED: MODBUS RTU communication failure
OFF: MODBUS RTU communication inactive
LED101
MODBUS TCP status
GREEN: MODBUS TCP communication success
RED: MODBUS TCP communication failure
OFF: MODBUS TCP communication inactive
LED400
Ethernet Activity
RED: Ethernet connection activity, lit when sending
or receiving data.
LED401
Ethernet Link
GREEN: lit when 10Mbps or 100Mbps Ethernet link
detected.
Summary of Contents for GBC05CI
Page 1: ...PASARELAETHERNET ETHERNET GATEWAY Ethernet Gateway Communication Network...
Page 2: ......
Page 3: ...Communication Network Ethernet Gateway Edition April 2012 GBC05CI Rev C...
Page 4: ...ETHERNET GATEWAY POWER ELECTRONICS 2...
Page 6: ...ETHERNET GATEWAY POWER ELECTRONICS 4...
Page 43: ...POWER ELECTRONICS ETHERNET GATEWAY WEB SERVER CONFIGURATION 41 E N G L I S H...
Page 45: ...www power electronics com...