ETHERNET GATEWAY
POWER ELECTRONICS
30
ETHERNET GATEWAY CONFIGURATION
ETHERNET GATEWAY CONFIGU-
RATION
The IP address and the gateway parameters of the Power Electronics
Ethernet Gateway can be assigned to the board in two ways; using
MODSCAN or Web Server application.
4.1.
Configuration Switch
To enter into configuration mode, the following steps have to be
followed.
Turn off the gateway
– switch off the 24Vdc power supply
Switch on the jumper for configuration mode
Turn on the gateway
– switch on the 24Vdc power supply
Now the gateway will enter into configuration mode. In this mode only
the gateway communication related parameters have to be configured.
In configuration mode the MODBUS/RTU communication is
established with the 9600 BAUDS, odd parity, 8
– data bits and 1 –
stop bit. The usage and configuration of parameters are explained
below.
Now the gateway has to turn back to operational mode to apply
changes. For this, following steps has to be performed.
Turn off the gateway
Switch off the jumper for operational mode
Turn on the gateway
4.2.
Mode Selection
MODBUS
register
[CACHING_ENABLED]
address
[MODBUS
Address: 41502] is allocated to switch over different operation modes.
Summary of Contents for GBC05CI
Page 1: ...PASARELAETHERNET ETHERNET GATEWAY Ethernet Gateway Communication Network...
Page 2: ......
Page 3: ...Communication Network Ethernet Gateway Edition April 2012 GBC05CI Rev C...
Page 4: ...ETHERNET GATEWAY POWER ELECTRONICS 2...
Page 6: ...ETHERNET GATEWAY POWER ELECTRONICS 4...
Page 43: ...POWER ELECTRONICS ETHERNET GATEWAY WEB SERVER CONFIGURATION 41 E N G L I S H...
Page 45: ...www power electronics com...