233
REV
AL 182
Use, maintenance and warning instructions
MEDIUM PRESSURE REGULATOR
|
MAINTENANCE AND FUNCTIONAL CHECKS
|
REV. 00
EN
Step Action
55
Unscrew and remove screws (30), locking ring (8), reinforced gasket (7) and O-ring (93).
NOTICE!
Take care that the upper seal does not fall off.
56
Remove the O-ring (39) from the reinforced gasket (7) and replace it, taking care to lubricate it with synthetic
grease.
NOTICE!
Before inserting the replacement O-ring, clean the retaining slots with a cleaning solution.
57
Position the reinforced gasket (7) and the locking ring (8).
58
Insert and fix the screws (30) according to the following tightening torque:
• DN 1”: tab. 9.107
• DN 2”: tab. 9.108
NOTICE!
Tighten the screws according to the cross diagram in paragraph 9.4.2.2.
59
Position the control head inside the regulator body (1) with the indicator slide (16) visible and on axis with the
gas flow direction.
NOTICE!
Take care not to damage the plug profile (5).
60
Insert and fix the screws (31) according to the following tightening torque:
• DN 1”: tab. 9.107
• DN 2”: tab. 9.108
NOTICE!
Tighten the screws according to the cross diagram in paragraph 9.4.2.2.
61
Connect the pneumatic connections between the regulator and the respective control unit, including down-
stream pressure ports.
Tab. 9.151.
WARNING!
Ensure that all parts have been fitted correctly.
Summary of Contents for REVAL 182
Page 404: ......