392
REV
AL 182
EN
Use, maintenance and warning instructions
MEDIUM PRESSURE REGULATOR
|
TROUBLESHOOTING
|
REV. 00
Failure
Device
Possible causes
Service
Delayed shut-off
LAMINATION VALVE
AR100
Filter (5) clogged
Replace
PRESSURE REGULATOR
R44/SS
Lower diaphragm (16)
breakage
Replace
Upper diaphragm (16)
breakage
Replace
Upper O-ring (53)
not sealing
Clean and replace if needed
Lower O-ring (53)
not sealing
Clean and replace if needed
O-ring (11) not sealing
Clean and replace if needed
No sealing
of the O-ring (35)
Clean and replace if needed
Balancing piston (42)
locked
Clean and lubricate
O-ring (62) not sealing
Clean and replace if needed
SAFETY VALVE
VS/FI
No sealing
Check and clean if neces-
sary
VALVE 3/2
Outer O-rings (46) not
sealing
Clean and replace if needed
O-ring (47) not sealing
Clean and replace if needed
O-ring (48) not sealing
Clean and replace if needed
Pad (16) dirty or
damaged
Clean and replace if needed
HB/97 BUILT-IN
SLAM-SHUT VALVE
Stem (6) with friction
Clean and lubricate
Plug (71) with friction
Clean and lubricate
Balancing piston O-ring
(36) not sealing
Clean and replace if needed
VALVE 3/2
Gasket (16) locked
Clean and replace if needed
Clogged vents
Check and clean if neces-
sary
Summary of Contents for REVAL 182