8.13.3 - CALIBRATION OF PRESSURE SWITCHES MOD. 100
11
13
17
15
10
16
Fig. 8.44.
Calibration of pressure switches mod. 100
Adjust the maximum pressure (11) ring nut (13):
• anti-clockwise to decrease the slim-shut device tripping pressure;
• clockwise to increase the slim-shut device tripping pressure.
Turn the minimum pressure (17) ring nut (15):
• anti-clockwise to decrease the slim-shut device tripping pressure;
• clockwise to increase the slim-shut device tripping pressure.
NOTICE!
For calibration ranges, please refer to chapter 13 “Calibration tables”.
ATTENTION!
After calibration of the pressure switch, remove the lever to avoid interference with other objects on the
system.