Use, maintenance and warning instructions
MEDIUM PRESSURE REGULATOR
|
MAINTENANCE AND FUNCTIONAL CHECKS
|
REV. 00
EN
9.4.6.2 - 204/A SERIES PILOT DISCONNECTION AND R14/A PRE-REGULATOR
SFIATO
VENT
1
6
7
20
5
4
2
3
B
A
MOTORIZZAZIONE
IMPULSO
A VALLE
IMPULSO
DI MONTE
Fig. 9.78. 204/A + R14/A series pilot
To disconnect the 204/A pilot, proceed as in tab. 9.156 (see fig. 9.78):
Step Action
1
Disconnect the sensing lines between the 204/A pilot and the regulator by adjusting the fittings (1, 2, 3).
2
Unscrew and remove the fixing screw to remove the pilot 204/A from the regulator.
3
Remove the pipe (20) by adjusting the fittings (4, 5).
4
Unscrew and remove the screw (6) to separate the R14/A pre-regulator from the pilot 204/A.
5
Undo and remove the screw (7) from pilot 204/A.
Tab. 9.155.
LOADING
VENT
SENSING ELE-
MENT
DOWNSTREAM
UPSTREAM
SENSING
ELEMENT