394
REV
AL 182
EN
Use, maintenance and warning instructions
MEDIUM PRESSURE REGULATOR
|
TROUBLESHOOTING
|
REV. 00
Failure
Device
Possible causes
Service
Downstream pressure
increase with slam-shut
device shutting off
HB/97 BUILT-IN
SLAM-SHUT VALVE
Reinforced gasket (8) dirty
or damaged
Clean and replace if needed
O-ring (39) not sealing
Clean and replace if needed
Plug profile (71) damaged
Replace
O-ring (88) not sealing
Clean and replace if needed
O-ring (87) not sealing
Clean and replace if needed
BYPASS DEVICE
HP2/2
O-ring (21) not sealing
Clean and replace if needed
Damaged seat profile (6)
Replace
Pad (12) dirty or damaged
Clean and replace if needed
O-ring (24) not sealing
Clean and replace if needed
Tab. 10.190.