386
REV
AL 182
EN
Use, maintenance and warning instructions
MEDIUM PRESSURE REGULATOR
|
TROUBLESHOOTING
|
REV. 00
Failure
Device
Possible causes
Service
Downstream pressure
increases
PRE-REGULATOR R14/A
Plug (5) damaged
Replace
204/A SERIES PILOTS
Plug (17) damaged
Replace
Diaphragm holder (16) and
plug (17) assembly locked
in open position
Check and clean if neces-
sary
Plug spring (21) collapsed
Replace
Downstream sensing line
obstructed
Clean
PM 182 MONITOR
Reinforced gasket (8) dam-
aged
Replace
Ice between reinforced
gasket (8) and plug (71)
Increase the regulator gas
inlet temperature
Soiling between reinforced
gasket (8) and plug (71)
Clean and check
gas filtration
Plug (71) locked
Clean and check the
movements
Control element assembly
tightening defective
Tighten properly
Transfer hole clogged
Clean
Plug guide O-ring (35)
damaged
Replace
Stem guide O-ring (36)
frictions
Lubricate and replace
if necessary
I/DWR (52) frictions
Lubricate and replace
if necessary
I/DWR (51) friction
Lubricate and replace
if necessary
Spring (80) collapsed
Replace
Summary of Contents for REVAL 182