Screen name Parameters
Values
Notes
Meter
Meter type
0.75" paddle
0.75" turbine
1.00" paddle
1.25" turbine
1.50" paddle
1.50" turbine
2.00" paddle
3.00" paddle
Generic
Only available when meter regeneration type
is selected.
Select the type of meter installed with the
system. A generic option is available if the
installed meter does not match any other
selection. Selecting the generic meter type
requires setting the number of pulses per
gallon or litre to ensure proper metering.
Generic
0,1 - 999.9 pulses per
gallon
1 – 1500 pulses per
litre
Only available when generic meter type is
selected.
Continuous
flow detect
ON
OFF
If set ON, gives an alarm if continuous flow is
detected at the outlet.
Setting
review
Displays a summary of all programmed settings.
Water Saver
Regen
Water saver
regen.
OFF
-
Remote
regeneration
Remote
signal
duration
1 – 255 seconds
OFF
Set the timing for contact closure in seconds