Installer manual Fleck 5800 XTR - Programming
68 / 126
Ref. MKT-IM-006 / E - 12.11.2019
Screen name Parameters
Values
Notes
Cl generation
Low salt
Cl generation
/
Low salt
OFF
ON
Low salt detect.
This parameter will not be available for filter
regeneration types.
On the valves of series 5800, cl generation/
low salt must be set OFF because the
chlorine cell kit managed by the XTR is not
available for those valves.
If set ON, chlorine generation together with
low salt detection will be performed during
brine draw cycle.
If set "Low salt detec.", only low salt
detection will be performed during brine
cycle.
Regen
interval
1 - 255
Regeneration
Only available when cl generation/low salt is
set ON.
This parameter determines the regeneration
frequency on which there will be chlorine
generation.
Low salt detection will be performed during
regenerations indifferently of the frequency
set for cl generation.
Salt alarm will not avoid scheduled
regenerations to be performed.
6.3.3
Format screen
From the master settings screen press the
format
button to display the format screen.
Format
language
units
hardness units
mg/L
metric
english
language:
Displays the language used on the controller: English, French, German, Italian,
Spanish, Dutch or Portuguese.
units:
Contains settings for the unit type (either US or Metric) to be used in the controller.
hardness units
: Contains settings for hardness units of measure (grains per gallon, mg/L or ppm,
German degrees, French degrees, or Clark degrees).