Installer manual Fleck 5800 XTR - Programming
66 / 126
Ref. MKT-IM-006 / E - 12.11.2019
Screen name Parameters
Values
Notes
Regeneration Regeneration
flow
Downflow
Downflow 2x BW
Upflow
Custom downflow
Custom upflow
Variable refill
Filter
Custom filter
Cycle steps on the home screen and during
regeneration will change to reflect the cycle
steps and order in the selected regeneration
flow.
Additional regeneration screen parameters
are dependent upon selected regeneration
flow. Not all parameters will be displayed,
depending of the selected regeneration flow.
Custom upflow, downflow and filter allows
for up to 20 programmable cycle steps.
Variable refill calculates refill time based on
salt dosage, media volume, and BLFC Size,
and it is not possible to change it.
Time per cycle step can be programmed for
all other regenerant flow options.
Relay output
Aux.1/Aux.2
Alarm based
Cycle based
Time based
Volume based
Off
For cycle based relays, select the cycle steps
on which the relays will turn on. For time
based relays, two start/end times can be
selected for each relay. Relay times are
based on total regeneration cycle time.
Volume based relays can be programmed
from one gallons/litres to the full system
volume capacity. Duration can be set from
one second to two hours. Volume based
option is not available when regeneration
type is set to time clock. Alarm based relays
will turn on when an alarm condition is met,
and will turn off when the alarm is cleared.