Installer manual Fleck 5800 XTR - Programming
64 / 126
Ref. MKT-IM-006 / E - 12.11.2019
Screen name Parameters
Values
Notes
Format,
Assistance
name
Free-form
text
A - Z and space
Name of service provider to display when
viewing the assistance screen. 24 character
limit.
Format,
Assistance
phone
Free-form
text
0 - 9 and space
Phone number of service provider to display
when viewing the assistance screen.
14 character limit.
Format,
Assistance
interval
Interval
Month based: 1 - 60
Regen based: 5 -
2000
OFF
Set to automatically display the assistance
screen after a certain number of months or
regenerations.
Valve
System
4
Type 4 (single system) is currently the only
available selection.
Valve
5800
5810
5812
Select the type of valve to be installed.
Regen type
Time clock
Softener immediate
Softener delayed
Filter immediate
Filter delayed
Regeneration types are described in detail on
Regeneration flows [
Additional Valve screen parameters are
dependent upon selected regeneration type.
Not all parameters will be displayed.
Softener delayed regeneration type has four
reserve options (fixed %, fixed volume,
variable reserve, weekly reserve). The
control will display additional configuration
options depending on the selected reserve
type.
Media
volume
0.25 to 999 ft
3
1 to 9999 litres
Only required on softener metered
regeneration types.
Salt dosage
3 to 18 lbs/ft
3
50 to 290 g/litre
BLFC size
0.125 gpm
0.250 gpm
0.500 gpm
1.000 gpm