Installer manual Fleck 5800 XTR - Programming
Ref. MKT-IM-006 / E - 12.11.2019
65 / 126
Screen name Parameters
Values
Notes
Valve
Capacity
1 to 999 999 grams
1 to 9 999 999 grains/
degrees
* Litre
Only required on softener metered systems
to calculate treated water capacity and
reserve. Represents total system capacity
between regenerations.
Hardness
1 – 199 grains/gallon
1 – 1999 mg/litre
x - x degrees
Only required on softener metered systems
to calculate treated water capacity and
reserve. Represents hardness of untreated
water.
Sensor
sensitivity
Not active
Not active
Day override
Time driven
OFF - 1 – 99 days
4, 8, 12, 16 and
20 hours
Mandatory for timeclock systems.
Available to be programmed for all
regeneration types.
4 to 20 hours setting available only for the
timeclock systems
Regeneration
time
12/24 hours clock
Required for time clock and delayed
regeneration types. Set for immediate
regeneration types only when a day override
is also set.
Not available for timeclock system if day
override is set from 4 to 20 hours.
Reserve
Fixed %
Fixed volume
Weekly reserve
Variable reserve
Only available when softener meter delayed
regeneration type is selected.
Selecting fixed % or fixed volume will display
additional configuration options.
Weekly reserve is calculated based on
average day of week's water usage.
Variable reserve is calculated based on
previous day's water usage.
Volume
override
1 to 999 999 999
gallons/litres
Only displayed when regeneration type is
filter immediate or filter delayed.