Note:
4communication setting value is relative percentage(-100. 00%
~
100.
00% ) , and can make communication write operations.When setting as
frequency source, relative is the largest frequency(F00.03);When setting as
torque source, relative is F03.10,F15.48 (motor1,motor2.)
Chapter 8 Appendix
Address
Data meaning
1F00H
******
Parameter lock password calibration: (if back to 8888H, is means password cali-
bration passed)
Status address
Command Function
1F01H
0001H: factory reset, not include motor parameter
0002H: clear fault file
Parameter initializing address is 1F01H:
AC Drive fault address
AC Drive fault information
8000H
0000H: no fault
0001H: acceleration overcurrent( E004)
0002H: deceleration overcurrent( E005)
0003H: constant speed overcurrent( E006)
0004H: acceleration overvoltage
(
E002
)
0005H: deceleration overvoltage
(
E00A
)
0006H: constant speed overvoltage
(
E003
)
0007H: undervoltage falut( E001)
0008H: motor overload
(
E007
)
0009H: AC drive overload( E008)
000AH: input phase loss
(
E012
)
000BH: output phase loss
(
E013
)
000CH: module overheat
(
E00E
)
000DH: buffer resistance overload( E014)
000EH: contactor fault( E017)
000FH: external fault( E00d)
0010H: communication fault( E018)
0011H: current detection fault
(
E015
)
0012H: motor self- learning fault
(
E016
)
Parameter initializing address is 1F01H:
-210-