Chapter 6 Description of Function Codes
Group F03: Vector Control Parameters
Group F03 is valid for vector control, and invalid for V/F control.
Function
code
Name
Description
(setting range)
Factory
Default
Change
F03.00
Proportional gain 1 of
speed loop
1
~
100
30
※
F03.01
Integral time 1 of speed
loop
0.01s
~
10.00s
0.50s
※
F03.02
Switchover low point
frequency
0.00Hz
~
F03.05
5.00Hz
※
F03.03
Proportional gain 2 of
speed loop
1
~
100
20
※
F03.04
Integral time 2 of speed
loop
0.01s
~
10.00s
1.00s
※
F03.05
Switchover high point
frequency
F03.02
~
F00.03( max.
frequency)
10.00Hz
※
Speed loop PI parameters vary with running frequencies of the AC drive.
If the running frequency is less than or equal to "Switchover frequency 1" (F03.02), the speed
loop PI parameters are F03.00 and F03.01.
If the running frequency is equal to or greater than "Switchover frequency 2" (F03.05), the
speed loop PI parameters are F03.03 and F04.04.
If the running frequency is between F03.02 and F03.05, the speed loop PI parameters are
obtained from the linear switchover between the two groups of PI parameters.
Fig.6-5
Relationship between running frequencies and PI parameters
F
3
.
02
F
3
.
05
Frequency
command
PI
parameters
(
F03.00
,
F03.01
)
(
F03.03
,
F03.04
)