Chapter 6 Description of Function Codes
These parameters are used to set the delay time of output terminals HDO, relay 1, relay 2,
MO1 from status change to actual output.
Function
code
Name
Description
(setting range)
Factory
Default
Change
F07.12
HDOP output selection
0~15
0
※
F07.13
Ao1 output selection
0
※
F07.14
Ao2 output selection
1
※
The output pulse frequency of the HDOP terminal ranges from 0.01 kHz to "HDO output
max.frequency" (F07.22). The value of F07.22 is between 0.01 kHz and 100.00kHz.
The output range of AO1 and AO2 is 0–10V or 0–20mA. The relationship between pulse and
analog output ranges and corresponding functions is listed in the following table:
Value
Function
Description
0
setting frequency
0 to maximum output frequency
1
running frequency
0 to maximum output frequency
2
output current
0 to 2 times of rated motor current
3
output voltage
0 to 1.2 times of rated AC drive voltage
4
output speed
0 to rotational speed corresponding to maximum
output frequency
5
output torque
0 to 2 times of rated motor torque
6
output power
0 to 2 times of rated power
7
pulse input
0.01kHz
~
100.00kHz
8
AI1
0V
~
10V
9
AI2
0V
~
10V
(
or 0
~
20mA
)
10
AI3
0V
~
10V
11
lenth
0 to maximum set length
12
count value
0 to maximum count value
13
Rs485 communication 0.0%
~
100.0%
14
output current 100%
corresponding to
1000.0A
0.0A
~
1000.0A
-150-