Function
code
Name
Description
(setting range)
Factory
Default
Change
48: external stop terminal 2
49: deceleration DC braking
50: clear the current running
time
F06.10
Input terminal valid
mode selection 1
0: valid on high level
1: valid on low level
units' digit: S1
tens' digit: S2
hundreds' digit: S3
thousands' digit: S4
ten thousands' digit: S5
00000
●
F06.11
Input terminal polarity
selection 2
0: valid on high level
1: valid on low level
units' digit: S6
tens' digit: S7
hundreds' digit: S8
thousands' digit: S9
ten thousands' digit: HDI
00000
●
F06.12
Filtering time of switch 0.000s
~
1.000s
0.010s
※
F06.13
Terminal control
operation mode
0: 2-wire control 1
1: 2-wire control 2
2: 3-wire control 1
3: 3-wire control 2
0
●
F06.14
Terminal UP/DOWN
rate
0.001Hz/s
~
65.535Hz/s
1.00Hz/s
※
F06.15
S1 delay time
0.0s
~
3600.0s
0.0s
●
F06.16
S2 delay time
0.0s
~
3600.0s
0.0s
●
F06.17
S3 delay time
0.0s
~
3600.0s
0.0s
●
F06.18
AI1 lower limit
0.00V
~
F06.20
0.00V
※
F06.19
Corresponding setting
of AI1 lower limit
-100.0%
~+
100.0%
0.0%
※
F06.20
AI1 upper limit
F06.18
~+
10.00V
10.00V
※
Chapter 5 Function & Parameter Table
-62-
C
h
a
p
te
r
5
Peaco Support FC280 Series VFD User Manual