Chapter 6 Description of Function Codes
-189-
Function
code
Name
Description
(setting range)
Factory
Default
Change
F13.03
Response delay
0ms
~
20ms
20
※
Communication response delay: It refers to the interval time from the end of the inverter's
data reception to the time when the data is sent to the upper computer. If the response delay
is less than the system processing time, the response delay is subject to the system proces-
sing time. If the response delay is longer than the system processing time, after the system
has processed the data, it will wait for a delay until the response delay time expires before
sending to the host computer. send data.
Function
code
Name
Description
(setting range)
Factory
Default
Change
F13.04
Communication timeout
0.0
(
invalid
),
0.1s
~
60.0s
0.0
※
When the function code is set to 0.0s, the communication timeout fault time parameter is
invalid.
When the function code is set to a valid value, if the interval between one communication
and the next communication exceeds the communication timeout time, the system will report
a communication failure error (E018).
Normally, it is set to invalid. If this parameter is set in a continuous communication system,
the communication status can be monitored.
Function
code
Name
Description
(setting range)
Factory
Default
Change
F13.05
Modbus protocol
selection
0: Non-standard Modbus
protocol
1: Standard Modbus protocol
0
※
F13.05= 1: Select standard Modbus protocol.
F13.05= 0: When reading the command, the number of bytes returned by the slave is one
byte more than the standard Modbus protocol.
Function
code
Name
Description
(setting range)
Factory
Default
Change
F13.06
Communication reading
current resolution
0: 0.01A
1: 0.1A
0
※
C
h
a
p
te
r
6
Peaco Support FC280 Series VFD User Manual