12 TERMINAL
BLACK
RED
GREEN
COM TERMINAL
14 TERMINAL
GROUND
(Terminal Block
applications
only)
GROUND
(All other
applications))
14
12
Introduction
Follow these instructions when installing, operating, or servicing
the product.
Port Identification / Connections / Symbols
Port
Single
Dual
No.
Pressure
Pressure
1
Inlet
Exhaust
2
Outlet
Outlet
3
Exhaust
Inlet
4
Outlet
Outlet
5
Exhaust
Inlet
12, 14
Pilot ports for External
Pilot or Remote Pilot
Application Limits
These products are intended for use in general purpose compressed
air systems only. Compliance with the rated pressure, temperature,
and voltage is necessary - see Installation & Service Instructions
(V-440P) packed with valve.
Operating Pressure Range:
Maximum 145 PSIG (1000 kPa)
Ambient Temperature Range:
-15°C to 49°C (5°F to 120°F)
Installation & Service Instructions
V-443P
F & H ISO 5599-2 Manifold Installation
ISSUED: November, 2001
Supersedes: February, 2001
Rev. 1 NPR# R06988
Pneumatic Division
Richland, Michigan 49083
Pneumatic
Figure 1
Wiring Instructions
1. Follow all requirements for local and national electrical codes.
2. Remove end cover from base by backing off the two captive
screws. Reassemble cover to base by tightening screws from
0.8 to 1.0 Nm (7 to 9 in-lbs).
4 2
5
14
12
1 3
5 Port, 2-Position
5 Port, 3-Position
Center to Outlets
4 2
5
14
12
1 3
4 2
5
14
12
1 3
5 Port, 3-Position
All Ports Blocked
4 2
5
14
12
1 3
5 Port, 3-Position
Outlets to Ends
!
!
WARNING
To avoid unpredictable system behavior that can cause personal
injury and property damage:
• Disconnect electrical supply (when necessary) before installation,
servicing, or conversion.
• Disconnect air supply and depressurize all air lines connected to
this product before installation, servicing, or conversion.
• Operate within the manufacturer’s specified pressure, temperature,
and other conditions listed in these instructions.
• Medium must be moisture-free if ambient temperature is below
freezing.
• Service according to procedures listed in these instructions.
• Installation, service, and conversion of these products must be
performed by knowledgeable personnel who understand how
pneumatic products are to be applied.
• After installation, servicing, or conversion, air and electrical
supplies (when necessary) should be connected and the product
tested for proper function and leakage. If audible leakage is present,
or the product does not operate properly, do not put into use.
• Warnings and specifications on the product should not be covered
by paint, etc. If masking is not possible, contact your local
representative for replacement labels.
WARNING
FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE
PRODUCTS AND/OR SYSTEMS DESCRIBED HEREIN OR RELATED
ITEMS CAN CAUSE DEATH, PERSONAL INJURY AND PROPERTY
DAMAGE.
This document and other information from Parker Hannifin Corporation,
its subsidiaries and authorized distributors provide product and/or
system options for further investigation by users having technical
expertise. It is important that you analyze all aspects of your application,
including consequences of any failure and review the information
concerning the product or systems in the current product catalog. Due
to the variety of operating conditions and applications for these products
or systems, the user, through its own analysis and testing, is solely
responsible for making the final selection of the products and systems
and assuring that all performance, safety and warning requirements of
the application are met.
The products described herein, including without limitation, product
features, specifications, designs, availability and pricing, are subject to
change by Parker Hannifin Corporation and its subsidiaries at any
time without notice.
!
WARNING
Air exhausting from one valve into the exhaust gallery of the manifold
assembly may momentarily pressurize other valve circuits open to the
same gallery. Design the circuit such that there is no hazard or
consequence of damage from this action.
3. An external ground connection must be attached to the green
ground screw of every base in an assembly.
4. Disregard unused wires or terminals.
Connections
14 Solenoid
12 Solenoid
Valves with Wires
Black Wires
Red Wires
Valves with Terminal Block
14 and Com
12 and Com
(Will accept 18 to 24 Gauge Wires)
Terminals
Terminals
Wiring - Auto C, F, G
3-Pin Mini
4-Pin M12 -
5-Pin Mini
Encl ‘1’, ‘7’
Encl ‘2’, ‘4’, ‘8’
Encl ‘3’, ‘5’, ‘9’
Wiring Type
C, F, G
C
F
G
C
F
G
Pin #1
Grd
14
N/A
12
12
14
12
Pin #2
14
Grd
12
N/A
12
12
14
Pin #3
Com
Com
Com
Com
Grd
Grd
Grd
Pin #4
N/A
12
14
14
14
12
14
Pin #5
N/A
N/A
N/A
N/A
14
14
12
Pin 1
(Green)
Pin 1
(Brown)
Pin 1
(White)
Pin 5
(Black)
Pin 2
(Red)
Pin 3
(Green)
Pin 4
(Orange)
Pin 4
(Black)
Pin 2
(White)
Pin 3
(Blue)
Pin 2
(Black)
Pin 3
(White)
!
CAUTION: An interruption of 10 milliseconds or greater to
the power supplied to the solenoid of a solenoid operated
valve may cause the valve to shift. Provision must be
made to prevent power interruption of this duration to
avoid unintended, potentially hazardous, consequences.