11.5.2 Wiring to FP2/FP2SH/FP3/FP10SH
Connect the RS485 interfaces on the I/O link unit and on the other station of the
FP2/FP2SH/FP3/FP10SH remote I/O system [MEWNT-F] with a 2-conductor cable (VCTF0.75 mm
2
x
2C (JIS).
Connects to the FP2/FP2SH/FP3/FP10SH system via [MEWNET-F].
When connecting the transmission cable, be sure to connect postive (+) to positive, and negative (-) to
negative of RS485 interfaces.
* Connect one end of the shielded line of the transmission cable to the F.G. terminal, and ground it.
-
Set the appropriate I/O link units in the transmission line of [MEWNET-F] as the terminal stations with
the mode selector switches SW1 & SW2.
Reference:
For information on the transmission cable specifications, <3.4 Transmission Cable Specifications>
For information on the connection of transmission cables and the setting of terminal station, <Chapter 5
Connection for the Remote I/O System>
11.5.3 Wiring of Power Supply
Supply power to the control unit, expansion unit, I/O link unit from the same power source so that power
ON and OFF for all units can be performed at teh same time.
Note:
Do not supply power to the DC power supply type unit from the terminal that supplies power for the input
of the FP1 control unit or expansion unit.
Summary of Contents for MEWNET-F
Page 9: ...Chapter 1 Functions and Restrictions of the Unit ...
Page 19: ...Chapter 2 Part Names and Functions ...
Page 40: ...2 22 ...
Page 41: ...Chapter 3 Unit Specifications ...
Page 52: ...3 12 ...
Page 53: ...Chapter 4 Installation and Wiring ...
Page 62: ...4 10 ...
Page 63: ...Chapter 5 Connection for the Remote I O System ...
Page 75: ...Chapter 6 Remote I O Map ...
Page 84: ...6 10 ...
Page 85: ...Chapter 7 Operation Modes for Controlling MEWNET F ...
Page 97: ...Chapter 8 Control by MEWNET F ...
Page 108: ...8 12 Flowchart ...
Page 110: ...8 14 ...
Page 111: ...Chapter 9 Troubleshooting ...
Page 120: ...9 10 ...
Page 121: ...9 11 9 5 2 When the ALARM LED is ON ...
Page 122: ...9 12 9 5 3 When the Communication LED on the Master Unit does Not Flash Normally ...
Page 123: ...9 13 When the COMM LED is OFF ...
Page 124: ...9 14 When the COMM LED is ON ...
Page 125: ...9 15 9 5 4 When the Communication LED on a Slave Station does Not Flash Normally ...
Page 126: ...9 16 When the COMM LED is OFF ...
Page 127: ...9 17 When the COMM LED is ON ...
Page 128: ...9 18 9 5 5 When the CPU does Not Operate ...
Page 129: ...9 19 9 5 6 When the Input Output Function of a Slave Station does Not Work ...
Page 130: ...9 20 9 5 7 When the Memory Access Function for the Advanced Unit s Memory does Not Work ...
Page 134: ...9 24 ...
Page 135: ...Chapter 10 Dimensions ...
Page 136: ...10 2 10 1 FP2 Multi wire Link Unit AFP2720 10 2 FP3 Remote I O Master Unit AFP3742 ...
Page 137: ...10 3 10 3 FP2 Remote I OSlave Unit AFP2745 10 4 FP3 Remote I OSlave Unit AFP3745 ...
Page 141: ...10 7 10 8 FP0 I O Link Unit AFP0732 ...
Page 142: ...10 8 ...
Page 143: ...Chapter 11 Appendix 1 I O Link With FP1 ...
Page 147: ...11 5 11 3 Part Names and Functions ...
Page 159: ...Chapter 12 Appendix 2 I O Link With FP0 ...
Page 164: ...12 6 ...
Page 166: ......
Page 167: ......
Page 168: ...FAF 35E 1 200803 http www mew co jp ac e fasys 2008 ...