- 24 -
Operation Function
Selection of the run command
The M2X series inverter provides the following six types of operations depending on
whether frequency commands and run commands are entered through the operation panel
or the terminal block.
Speed command
Run command
Parameter
From
operation
panel, or
control dial
Terminal block
FIN1 or FIN2 on
terminal block
∗
2
Operation
panel
Terminal
block
Frequency command
selection
Run command
selection
1
○
○
∗
1
○
∗
1
or
(both
)
2
○
○
∗
1
○
∗
1
or
(both)
3
○
○
or
(panel)
4
○
○
or
(panel)
5
○
○
or
(terminal block)
6
○
○
or
(terminal block)
Default settings of [
Frequency command selection] and [
Run command selection] are
and
, respectively.
Frequency command selection changing procedure
Example) Change [
Frequency command selection] from
to
.
Operation panel
Step
Switch
LED display
①
Power ON
②
Parameter
number mode
Press DATA SET
Using
△
, select the
parameter No.
③
Parameter set
value mode
Press DATA SET
Using
△
, select the
parameter value
Press DATA SET to
save the value
∗
1 The run command from the terminal block overrides the command from the operation panel, if both
are enabled.
The RUN switch on the operation panel is active only when both the CCW/stop switch (I1) and the
CW/stop switch (I2) on the terminal block are OFF. If both or one of [I1] and [I2] are turned on while
the RUN switch is active, the operation mode set from RUN switch is cancelled.
∗
2 The “FIN1” and “FIN2” terminals are intended for voltage command (0 to 5 VDC or 0 to 10 VDC) and
current command (4 to 20 mADC), respectively. For details, refer to “Terminal function: “(2) Control
Terminal” on P18.