40
Parameter Description
Parameter setting
No.
Parameter name
Adjustment range
Min. unit
Factory setting Check
∗
1
Acceleration time
5 sec
No.2 acceleration time
5 sec
No.3 acceleration time
5 sec
No.4 acceleration time
0 - 3600 sec
- 3 sec
3 sec - 10 sec
10 sec -
: in steps of 0.01 sec
: in steps of 0.1 sec
: in steps of 1 sec
5 sec
DC brake intensity
0 - 100
2
70
DC brake time
Case of
:
0 - 3 sec
Case of
-
:
0 - 6 sec
0.05 sec
0.1 sec
0.5 sec
1.0 sec
DC brake selection
Positioning
-
Full-range stop
Start-up brake time
0 - 3 sec
0.05 sec
0
(
Disabled
)
Brake starting
0.5 - 400Hz
0.01Hz
∗
3
3
Hz
Carrier frequency
0, 1, 2, 3, 4, 5, 6, 7
5
Deceleration time
5 sec
No.2 deceleration time
5 sec
No.3 deceleration time
5 sec
No.4 deceleration time
0 - 3600 sec
- 3 sec
3 sec - 10 sec
10 sec -
: in steps of 0.01 sec
: in steps of 0.1 sec
: in steps of 1 sec
5 sec
Base frequency
30 - 400Hz
1Hz
50Hz
Maximum output
0 - 100%
1%
100%
V/F reduction
characteristic
1.0 - 2.0 squared
0.1
1.0
2nd V/F selection
No selection
(Ordinary V/F pattern)
Upper pattern
Lower pattern
2nd V/F base frequency
30 - 400Hz
1Hz
50Hz
2nd V/F boost
0 - 100
2
0
Jump frequency width
0
- 400Hz
0.01Hz
∗
3
0Hz
Jump frequency
①
0, 0.5
∗
2
- 400Hz
0.01Hz
∗
3
0Hz
Jump frequency
②
0, 0.5
∗
2
- 400Hz
0.01Hz
∗
3
0Hz
Jump frequency
③
0, 0.5
∗
2
- 400Hz
0.01Hz
∗
3
0Hz
Jump frequency
④
0, 0.5
∗
2
- 400Hz
0.01Hz
∗
3
0Hz
∗
1 Parameters marked by
in the Check column are tripped for safety if modified or
memorized.
Cancel the trip before use.
∗
2 The lower limit of the adjustment range varies depending on the [
Starting frequency] setting.
∗
3 When the set value exceeds 160 Hz, the minimum unit of setting is 0.05 Hz.