64
Detailed Parameter Description
⑫
Write
parameter
into
inverter
Holding STOP ,
press
DATA SET
for 1 second.
•
2-digit and 5-digit LEDs flash.
⑬
Wait for
approx. 10
seconds
•
is displayed for
approx. 3 seconds.
⑭
Parameter
values have
been written
from the
operation
panel into the
inverter
circuits
•
Self-diagnosis trip occurs.
⑮
Return to
monitor mode
Simultaneously press
△
and
▽
to cancel trip.
•
Monitor mode
To copy parameter values to two or more inverters, use the master panel produced in [1] and repeat the
steps of [2].
∗
If parameters are not copied correctly,
or
is displayed followed by no
self-diagnosis trip.
To cancel the display, press STOP . For corrective action, refer to the description that follows.
Error message
Description
Corrective action
Parameter values to be copied are invalid.
The parameter values may have
been destroyed by external noises.
Press STOP and repeat steps
starting with <1. Initializing
operation panel>.
The copy is attempted between inverters of
different series.
Be sure to copy between the same
series.
After panel initialization, attempt is made to
write parameter value from the operation
panel into the inverter without first reading
parameter values in inverter out to the panel.
Press STOP and repeat steps
starting with <1. Initializing
operation panel>.