Aurora H2O User’s Manual
23
Appendix B. Aurora H2O Ethernet Operation
B.4 Communicating by MODBUS via Ethernet
The Aurora H2O Ethernet option supports two communications modes:
•
MODBUS/TCP over Ethernet
•
MODBUS/RTU over Ethernet
The Aurora H2O and the Ethernet option must be correctly configured for the desired communications mode.
B.4.1 MODBUS/TCP
Note:
As shipped, the Aurora H2O is configured to use the
Modbus/TCP
Ethernet protocol.
Select
MODBUS/TCP (MB/TCP)
from the Aurora H2O menu (
Main Menu, Settings…, Ethernet…,
Protocol
).
To use Modbus/TCP over Ethernet, the Ethernet module must also be configured as
follows:
1.
Log in to the web user interface. Either the root account or an operator account may be used to configure the
module.
2. Choose
Serial Ports
from the
Configuration Menu
. Verify that
Industrial Automation
is selected as the
Profile
(see
Figure 111
below).
3. Click on the
Port 1
link to display the current
Profile
.
Figure 111: MB/TCP Serial Port 1 Profile
3.
If the information displayed is not correct, change the profile as required.
Summary of Contents for Aurora H2O
Page 1: ...panametrics com 910 317 B August 2022 Aurora H2O User s Manual...
Page 2: ......
Page 4: ...ii no content intended for this page...
Page 12: ...Chapter x Aurora H2O User s Manual no content intended for this page...
Page 24: ...Chapter 1 Features and Capabilities 12 Aurora H2O User s Manual...
Page 44: ...Chapter 2 Installation 20 Aurora H2O User s Manual...
Page 47: ...Aurora H2O User s Manual 28...
Page 65: ...Chapter 3 Operation and General Programming 18 Aurora H2O User s Manual...
Page 96: ...Aurora H2O User s Manual 36...
Page 120: ...Chapter 5 AuroraView Interface Software 24 Aurora H2O User s Manual...
Page 140: ...Chapter 7 Troubleshooting 6 Aurora H2O User s Manual...
Page 148: ...Appendix A MODBUS RTU TCP Communications 14 Aurora H2O User s Manual...
Page 166: ...4 Aurora H2O User s Manual...
Page 168: ...Warranty 6 Aurora H2O User s Manual no content intended for this page...
Page 169: ......