Installing XLink
5.1
Attaching XLink 500 and 100
Requirements of the intended installation site are:
Sufficient protection from moisture for an IP 41 device.
Proper space for the electrical cables
Battery cable shall have an inline fast fuse to handle current up to 5A
Temperature range -40C to +70C.
Space for installation using the mounting ears
Earth ground point
Closed control cabinet or fire protection cabinet if the power supply is not a low power source 12-
20VDC.
A minimum 70C rated cable/wire is recommended to be used for installation.
The dimensions are shown in inches in the figure below along with the locations of the mounting ears.