VCB-X Operator Interface SD
MINILINK PD STATUS
77
MiniLink PD Con
fi
guration and Status Screens
Con
fi
guration Screen #4 - Optimal Start
Target Zone
Polling Unit Config
Optimal Start
Target Zone..: XXX
[Enter Target Zone]
This is the unit ID of the Zone that you want to be satis
fi
ed by the
normally scheduled start time. If you enter “-1” into this box, it will
average all zones instead of picking a speci
fi
c zone. If you do not require
Optimal Start, enter “0”.
Con
fi
guration Screen #5 - Maverick Testing
Polling Unit Config
Maverick Testing
Disabled: YES
Use < Or > To Change
Disabling the Maverick Testing allows known troubled zone(s) to
continue voting without causing a Maverick alarm. In other words, all
zones are included in the voting regardless of whether they are more
than four degrees from setpoint.
Con
fi
guration Screens #6-65 - Alarm Polling
Polling Unit Config
Enable Alarm Polling
Unit XX : YES
Use < Or > To Change
Enabling Alarm Polling allows any alarm from the loop to be polled.
You must set this for each controller on the loop.
MiniLink PD Status
Status Screen #1 - Schedule Mode, System
Status, and Minutes Left
Polling Device
System Occupied
Venting Mode
XXX Min Left in Mode
Line 2
Current Schedule Mode
Can be System Occupied or System Unoccupied.
Line 3
Currently System Status
Can be Vent Mode, Cooling Mode, or Heat Mode.
Line 4
Minutes Left In Mode
The number of minutes left in the current mode of
operation before it can switch modes. This value is
user-adjustable.
See
Con
fi
guration Screen #3.
Status Screen #2 - Mode Priority, Cool Total,
and Heat Total
Polling Device
No Mode Priority
Cool Total.: XX.X
º
F
Heat Total.: XX.X
º
F
Line 2 Mode Priority
Can be Heat Priority or Cool Priority. This is based on
the voting zones and their demand.
Line 3 Cool Total
Total cooling temperature demand from all zones.
Line 4 Heat Total
Total heating temperature demand from all zones.