VCB-X Operator Interface SD
VCB-X STATUS
59
VCB-X Status Screens
Status Screen 10 - Heating Outputs - Active
Stages and Mod Heat Position
VCB-X v2.00 ID 101
Heating Outputs
Active Stages: XX
Mod Heat Pos.: XXX%
If this is
not
a Heat Pump unit, the screen above will be shown.
Line 3
Heating Active Stages
This line will display the number of stages of Heating
that are currently active.
Line 4 Current Modulating Heating Output Signal Percentage
Indicates the percentage output signal being supplied
to a Modulating Heating device when you have con
fi
gured
this option for your HVAC unit.
Status Screen 11 - MODGAS-X Enabled and
Output %
VCB-X v2.00 ID 101
MODGAS-X
Enabled..: YES/NO
Position...: XXX%
Line 3 MODGAS-X Enabled or Disabled
This indicates whether the VCB-X Controller has enabled
the MODGAS-X Controller to begin to operate. If you do
not have a MODGAS-X Controller connected to the
VCB-X Controller, this line will indicate “NO”.
Line 4 Current MODGAS-X Heating Output Signal
Indicates the percentage output signal being supplied
by the MODGAS-X Controller when you have one
connected to the VCB-X Controller.
Status Screen 12 - Indoor RH & Indoor RH
Setpoint
VCB-X v2.00 ID 101
Indoor RH: XXX.X%
RH Spt: XXX.X%
Line 2 Current Indoor Relative Humidity Percentage
If an E-BUS Space Temperature/Humidity Sensor has been
installed
and
con
fi
gured on the unit, the current Indoor Air
Relative Humidity Percentage will appear on this line. If
this combination Temperature/Humidity Sensor is not
installed, this line will display 0%.
Line 3 Current Indoor Relative Humidity Setpoint Percentage
This is the adjustable Indoor Air Relative Humidity
Setpoint Percentage that has been set by the user.
Status Screen 13 - Coil (Saturation) Temp &
Setpoint & Suction Pressure
VCB-X v2.00 ID 101
Coil Temp: XXX.X
Coil Setpt: XXX.X
Suction Pr: XXX PSI
Line 2 Coil (Saturation) Temperature
If a Suction Pressure Transducer has been installed and
con
fi
gured on the unit, the calculated Evaporator Coil
(Saturation) Temperature will appear on this line. If not, this
line will display 0°F.
Line 3 Coil (Saturation) Temperature Setpoint
During
DX
dehumidi
fi
cation, compressor(s) will be staged/
modulated to maintain this Coil Suction Temperature
Setpoint. If indoor humidity reset of the Coil Setpoint has
been
con
fi
gured, this will be the current calculated setpoint.
Line 4 Suction Pressure
This is the current Suction Pressure.
Status Screen 14 - Active Reheat Stages
VCB-X v2.00 ID 101
Active Reheat
Stages: X
Line 3 Active Reheat Stages -
This screen is not currently used.
Status Screen 15 - MHGRV-X Enabled and
Output %
VCB-X v2.00 ID 101
MHGRV-X
Enabled: YES/NO
Position: XXX%
Line 3 MHGRV-X Enabled or Disabled
This indicates whether the VCB-X Controller has enabled
the MHGRV-X Controller to begin to operate. If you do
not have a MHGRV-X Controller connected to the
VCB-X Controller, this line will indicate “NO”.
Line 4 Current MHGRV-X Reheat Valve Output Signal
Percentage
Indicates the percentage output signal being supplied
by the MHGRV-X Controller when you have one
connected to the VCB-X Controller.