VAV/ZONE CONFIGURATION
VCB-X Operator Interface SD
68
VAV/Zone Con
fi
guration Screens
Con
fi
guration Screen #10 - Dump Zone
XX Box Cnfg IDXXXX
Is This A Dump Zone
(No Actuator): NO
Use < Or > To Change
A “Dump Zone” is used when you want to control a duct heater or
baseboard heater independently. A VAV/Zone Controller board with a
relay expansion board is used for this purpose. No damper or actuator
is used. If you need to control an auxiliary heater,
select
YES; otherwise,
be sure it is set to NO.
Con
fi
guration Screen #11 - HVAC Unit is on
Separate Loop
XX Box Cnfg IDXXXX
HVAC Unit is on
Separate Loop: NO
Use < Or > To Change
If this system has 1 HVAC unit controlling boxes on multiple loops and
the HVAC unit is on a different loop than this box,
select
YES; otherwise,
be sure it is set to NO.