VCB-X Operator Interface SD
VCB-X CONFIGURATION
55
Setpoint Screen #54 - Return Air Bypass
Damper Factor Setpoint
VCBX Spts ID 101
Return Air Bypass
Damper Factor
Setpoint: 0%
This setpoint is used when your HVAC unit is con
fi
gured for Return
Air Bypass Damper control. The Return Air Bypass Damper Factor
Setpoint is a percentage value that is used to calculate the Return Air
Damper position in relation to the Return Air Bypass Damper position.
This provides a method for adjusting the air
fl
ow through the Return
Air Bypass Damper.
Increasing this percentage increases the air
fl
ow through the Return Air
Bypass Damper by causing the Return Air Damper to move further
towards its closed position in relation to the Return Air Bypass Damper
moving towards its open position.
Description
Minimum
Default
Maximum
Damper Factor
0%
0%
100%
Setpoint Screen #55 - Warm-Up Supply Air
Temperature Setpoint
VCBX Spts ID 101
Warmup Supply Air
Setpoint: 100.0
º
F
Heating will be controlled to this Supply Air Setpoint during Morning
Warm Up and during Night Setback Heating in a Supply Air Temper-
ing application.
Description
Minimum
Default
Maximum
Warm-Up SAT Setpoint
40
100
240
Setpoint Screen #56 - Cool-Down Supply Air
Temperature Setpoint
VCBX Spts ID 101
Cooldown Supply Air
Setpoint: 55.0
º
F
Cooling will be controlled to this Supply Air Setpoint during Morning
Cool-Down and during Night Setback Cooling in a Supply Air Temper-
ing application.
Description
Minimum
Default
Maximum
Cool-Down SAT Setpoint
30
55
80
VCB-X Setpoint Screens
Setpoint Screen #57 - PREHEAT-X Cooling
Mode and Heating Mode Setpoints
VCBX Spts ID 101
Preheat-X Spts
Cooling Mode: 40.0
º
F
Heating Mode: 60.0
º
F
If using the Preheat-X Controller with the VCB-X, this screen allows
you to set the Preheat setpoint you want to control to during the Cooling
and the Heating Modes.
Description
Minimum
Default
Maximum
Preheat-X Cooling Mode
Setpoint
35.0ºF
(1.66
º
C)
40.0ºF
(4.5
º
C)
90.0ºF
(32.2
º
C)
Preheat-X Heating Mode
Setpoint
35.0ºF
(1.66
º
C)
60.0ºF
(15.5
º
C)
90.0ºF
(32.2
º
C)
Setpoint Screen #58 - PREHEAT-X Venting
Mode Setpoint
VCBX Spts ID 101
Preheat-X Spts
Venting Mode: 50.0
º
F
If using the Preheat-X Controller with the VCB-X, this screen allows you
to set the Preheat setpoint you want to control to during the Vent Mode.
Description
Minimum
Default
Maximum
Preheat-X Venting Mode
Setpoint
35.0ºF
(1.66
º
C)
50.0ºF
(10.0
º
C)
90.0ºF
(32.2
º
C)