VCB-X Operator Interface SD
VCB-X STATUS
63
Status Screen 32 - Leaving Water Temperature,
Entering Water Temperature & Suction Pressure
VCB-X v2.00 ID 101
Lvg H20 Tmp: XXX.XX
Suction Pr: XXX PSI
Line 2 Leaving Water Temperature
If you are using a Water Side Condenser and have a
Leaving Water Temperature Sensor connected to the EM1
Module, this line displays the Leaving Water Temperature
of
the
unit.
Line 3 Suction Pressure
This is the current Suction Pressure.
Status Screen 33 - Water Source Heat Pump
Module Setpoints - Heating and Cooling
VCB-X v2.00 ID 101
WSHP Spts XX% Glycol
Ht Mode Lo Suct: XXX
Cl Mode Lo Suct: XXX
If this unit has a Water Source Heat Pump Module, these values are
read directly from hard-coded information in that module. The values
on Lines 3 and 4 are safety setpoints that will disable compressors. See
the
Water Source Heat Pump Module Technical Guide
for further details
about these safeties.
Line 2 WSHP Glycol Percentage
This line displays the percentage of glycol that the Water
Source Heat Pump module is currently using.
Line 3 Heating Mode Low Suction Setpoint
This is the Heating Mode Low Suction Setpoint.
Line 4 Cooling Mode Low Suction Setpoint
This is the Cooling Mode Low Suction Setpoint.
Status Screen 34 - Water Source Heat Pump
Module Setpoints - Unsafe Suction and Leaving
Water Temperature
VCB-X v2.00 ID 101
WSHP Spts XX% Glycol
Unsafe Suction: XXX
Lo Lvg H20 Tmp: XXX
VCB-X Status Screens
If this unit has a Water Source Heat Pump Module, these values are
read directly from hard-coded information in that module. The values
on Lines 3 and 4 are safety setpoints that will disable compressors.
See the
Water Source Heat Pump Module Technical Guide
for further
details about these safeties.
Line 2 WSHP Glycol Percentage
This line displays the percentage of glycol that the Water
Source Heat Pump module is currently using.
Line 3 Unsafe Suction Setpoint
This is the Unsafe Suction Setpoint.
Line 4 Low Leaving Water Temperature
This is the Low Leaving Water Temperature Setpoint.
Status Screen 35 - Return Air Damper Signal
& Return Air Bypass Damper Signal
VCB-X v2.00 ID 101
Return Dmp..: XXX%
Bypass Dmp..: XXX%
[Optional Outputs]
Line 2 Current Return Air Damper Signal
If con
fi
gured for Return Air Bypass Control, this
indicates the current Output Signal percentage being
sent to the Return Air Damper Actuator. If you haven’t
con
fi
gured a Return Air Bypass Damper, [No Return
Dmp Confg] will be displayed instead.
Line 3 Current Return Air Bypass Damper Signal
Indicates the current Output Signal percentage being sent to
the Return Air Bypass Damper Actuator. If you haven’t
con
fi
gured a Return Air Bypass Damper, [No Bypass Dmp
Confg] will be displayed instead.
Line 4 Indicates That These Are Optional Outputs
This output may or may not have live data to display.
Status Screen 36 - Reset Voltage Signal
VCB-X v2.00 ID 101
Reset Voltage Signal
0.0VDC
Line 2-3 Reset Voltage Signal
If using a Remote Voltage Signal to reset the Supply Air
Temperature setpoint and you have an EM2 Expansion
Module installed and con
fi
gured, this screen will display the
current Reset Voltage Signal being sent to the controller.