Zone
Zone
VCB-X CONFIGURATION
VCB-X Operator Interface SD
34
VCB-X Con
fi
guration Screens
Con
fi
guration Screen #47 - Condenser Fan
Outputs
VCBX Cnfg ID 101
Cond Fan Max: 100%
Cond Fan Min: 15%
If using Head Pressure control, you can set the Max and Min signal
percentages on this screen. The EM1 Expansion Module must be in-
stalled and con
fi
gured.
Description
Minimum
Default
Maximum
Condenser Fan Max
0
100
100
Condenser Fan Min
0
15
100
Con
fi
guration Screen #48 - Has Water Side
Condenser
VCBX Cnfg ID 101
Has Water Side Cond.
NO
Use < Or > To Change
This con
fi
guration option is available if expansion module EM1 has been
installed and con
fi
gured and if using a Water Side Condenser. Select NO
if the unit is con
fi
gured as Water Source Heat Pump.
Default is NO.
Con
fi
guration Screen #49 - Type of Air
fl
ow
Station
VCBX Cnfg ID 101
Airflow
Station: Paragon
Use < Or > To Change
Select the type of Air
fl
ow Monitoring Station you are using, if any.
Selections are Paragon or Ebtron. Choose Ebtron if using Greentrol.
Default is Paragon
.
Con
fi
guration Screen #50 - Monitor Outdoor
Air Air
fl
ow
VCBX Cnfg ID 101
Monitor OA Airflow
NO
Use < Or > To Change
Select
YES if you have an Air
fl
ow Monitoring station measuring the
CFM of the Outdoor Air air
fl
ow stream of this unit.
Default is NO.
Con
fi
guration Screen #51 - Control Outdoor
Air CFM
VCBX Cnfg ID 101
Control Outdoor Air
CFM: NO
Use < Or > To Change
Select
YES if you have an Air
fl
ow Monitoring station and are controlling
the Outdoor Air Damper to an air
fl
ow (CFM) Setpoint.
Default is NO.
Con
fi
guration Screen #52 - Outdoor Air
fl
ow
Duct Size
VCBX Cnfg ID 101
Outdoor Airflow Duct
Size: 000.00
[In Square Feet]
For the controller to properly calculate the Outdoor Air CFM, you need
to
enter
the area in square feet of the Outdoor Air duct/damper. When
measuring the Outdoor Air duct damper area, be sure to measure the
inside dimensions of the damper. The duct size needs to be accurate to
two decimal places. The more accurate the measurements, the more
accurate the CFM reading will be.
Default is 0.
Description
Minimum
Default
Maximum
Outdoor Air Air
fl
ow Duct Size
0
0
200.00
Con
fi
guration Screen #53 - Monitor Supply Air
Air
fl
ow
VCBX Cnfg ID 101
Monitor SA Airflow
NO
Use < Or > To Change
Select
YES if you have an Air
fl
ow Monitoring station measuring the
CFM of the Supply Air air
fl
ow stream of this unit.
Default is NO.
Con
fi
guration Screen #54 - Supply Air
fl
ow
Duct Size
VCBX Cnfg ID 101
Supply Airflow Duct
Size: 000.00
[In Square Feet]
For the controller to properly calculate the Supply Air CFM, you need
to
enter
the area in square feet of the Supply Air duct/damper. When
measuring the Supply Air duct damper area, be sure to measure the
inside dimensions of the damper. The duct size needs to be accurate
to two decimal places. The more accurate the measurements, the more
accurate the CFM reading will be.
Default is 0
.