VCB-X Operator Interface SD
VCB-X CONFIGURATION
35
Description
Minimum
Default
Maximum
Supply Air Air
fl
ow Duct Size
0
0
200.00
Con
fi
guration Screen #55 - Monitor Return Air
Air
fl
ow
VCBX Cnfg ID 102
Monitor RA Airflow
NO
Use < Or > To Change
Select
YES if you have an Air
fl
ow Monitoring station measuring the
CFM of the Return Air air
fl
ow stream of this unit.
Default is NO.
Con
fi
guration Screen #56 - Return Air
fl
ow
Duct Size
VCBX Cnfg ID 101
Return Airflow Duct
Size: 000.00
[In Square Feet]
For the controller to properly calculate the Return Air CFM, you need
to
enter
the area in square feet of the Return Air duct/damper. When
measuring the Return Air duct damper area, be sure to measure the inside
dimensions of the damper. The duct size needs to be accurate to two
decimal places. The more accurate the measurements, the more accurate
the CFM reading will be.
Default is 0.
Description
Minimum
Default
Maximum
Return Air Air
fl
ow Duct
Size
0
0
200.00
Con
fi
guration Screen #57 - Monitor Exhaust
Air
fl
ow
VCBX Cnfg ID 101
Monitor Exh Airflow
NO
Use < Or > To Change
Select
YES if you have an Air
fl
ow Monitoring station measuring the
CFM of the Exhaust Air air
fl
ow stream of this unit.
Default is NO.
Con
fi
guration Screen #58 - Exhaust Air
fl
ow
Duct Size
VCBX Cnfg ID 101
Exhaust Airflow Duct
Size: 000.00
[In Square Feet]
For the controller to properly calculate the Exhaust Air CFM, you need
to
enter
the inside area in square feet of the Exhaust Air duct/damper.
When measuring the Exhaust Air damper area, be sure to measure the
inside dimensions of the damper. The duct size needs to be accurate to
two decimal places. The more accurate the measurements, the more
accurate the CFM reading will be.
Default is 0
.
Description
Minimum
Default
Maximum
Exhaust Air
fl
ow Duct Size
0
0
200.00
Con
fi
guration Screen #59 - Morning Warm Up
VCBX Cnfg ID 101
Morning Warm Up
None
Use < Or > To Change
You can choose between the following Morning Warm Up options.
Default is None.
Available options are:
None
— There is no Morning Warm Up required.
Stand Alone
—
The VCB-X Controller is not
communicating to Orion VAV Box controls, but a Morning
Warm Up Relay can be con
fi
gured to signal boxes by others
to
open.
Bcast Fixed to Boxes
—The VCB-X Controller is
communicating to Orion VAV Boxes and will broadcast
a command to the boxes to go to a Fixed Percentage
Position
or
Air
fl
ow while in Morning Warm Up. This
fi
xed
position is con
fi
gured in the VAV Box Controller.
Bcast Max to Boxes
—The VCB-X Controller is
communicating to Orion VAV Boxes and will broadcast
a command to the boxes to go to a Maximum Percentage
Position
or
Air
fl
ow while in Morning Warm Up. This
maximum position is con
fi
gured in the VAV Box Controller.
Con
fi
guration Screen #60 - AHU Uses
Schedule Number
VCBX Cnfg ID 101
AHU Uses Schedule
Number: 0
[‘0’ For Internal]
The VCB-X has an internal schedule. If you want the VCB-X to use its
own internal schedule,
enter
<0>
for Internal.
VCB-X Con
fi
guration Screens