2-2
Section
Wiring
14
2-2
Wiring
2-2-1
I/O Signals
Brown
Blue
White
Gray
Black
Shield
(1) 12 to 24 VDC
(2) 0 V
(3) HIGH/PASS output
(4) LOW/NG output
(5) Linear output (1 to 5 V)
(6) Linear GND
Green
Purple
Red
Orange/Purple
Pink
(7) Bank selection input
(8) Timing input
(9) Hold reset input
(10) Forced-zero input
(11) LD OFF input
(1)12 to 24 VDC
Power terminal. Connect to 12 to 24 VDC power supply.
(2)0 V
0 V power terminal. Also, common terminals for forced zero
input, timing input, and LD OFF input.
(3)HIGH Output
Turns ON when the measured value is less than or equal to
the HIGH threshold. (Depends on the discrimination output
methods.)
PASS Output
Turns ON when the measured value is above the LOW
threshold and below the HIGH threshold. (Depends on the
discrimination output methods.)
(4)LOW Output
Turns ON when the measured value is equal to or greater
than the LOW threshold. (Depends on the discrimination
output methods.)
NG Output
Turns ON when the measured value is equal to or less than
the LOW threshold or equal to or greater than the HIGH
threshold. (Depends on the discrimination output methods.)
(5)Linear Output (1 to 5 V)
Outputs 1 to 5 VDC in proportion to light received or inter-
rupted. (Selectable with light/dark mode switch)
(6)Linear GND
Connect to input device as linear output GND.