What can be done by the setting tool
2. Non-Sequential Beam Mode
When total number of interrupted beams in an zone reaches the designated number or more, it is
evaluated as interruption.
• Setting Example
If number of floating beams is 2, safety output is not turned OFF if 3 or more beams are interrupted.
If 2 or less beams are interrupted, safety output is not turned OFF. (Figure 5)
If 3 or more beams are interrupted, safety output is turned OFF. (Figure 6)
Even if there is only one interrupting object, safety output can be turned OFF when 3 beams are
interrupted. (Figure 7)
• Internal Indicators of F3SJ
For basic system: Emitter’s BLANKING/TEST indicator is turned on under floating blanking state.
For muting system: Receiver’s BLANKING/TEST indicator is turned on under floating blanking state.
3 or more beams are interrupted
2 or less beams are interrupted
3th beam
13th beam
3th beam
13th beam
Figure 5
Figure 6
Floating blanking zone
Floating blanking zone
Safety output OFF
Safety output ON
An interrupting object blocks 3 or more beams
3th beam
13th beam
Figure 7
Floating blanking zone
Safety output OFF