75
F3SJ-A
User’s Manual
Ch
apt
e
r
3
Set
ting Adjust
ed
to Appl
ication
What can be done by the setting tool
E
Setting Example: F3SJ-A
P20 series
If number of floating beams is 3, minimum detection capability is 65mm.(Figure 1)
If number of floating beams is 3, and if diameter of an interrupting object is 40mm or smaller, safety
output is not turned OFF. (Figure 2)
If monitoring function is enabled and number of allowable beams is 2, the F3SJ locks out if an
interrupting object is removed or its diameter gets smaller than 20mm. (Figure 3)
Safety output can be turned OFF when more than one zone is interrupted by object(s) that should not
turn the safety output OFF. (Figure 4)
Safety output OFF
Not specified
Dia. 65mm
Floating blanking zone
Floating blanking zone
Figure 1
Figure 2
13th beam
13th beam
3rd beam
3rd beam
Safety output does
not turn OFF
Setting number of floating beams to 3
Interrupting object diameter 40mm max.
Dia. 40mm
Lockout
Interrupting object diameter 20mm max.
Interrupting object is removed
More than one zone is interrupted
Figure 3
Figure 4
Safety output OFF
Floating blanking zone
Floating blanking zone
13th beam
3rd beam
13th beam
3rd beam
Dia. 20mm max.
Dia. 30mm
Dia. 30mm