Appendices
A - 24
NX-series IO-Link Master Unit User’s Manual (W567)
Index
(hex)
Subindex
(hex)
Object name
Default
value
Data range
Unit
Data
type
Access
I/O allo-
cation
Data
attribute
5003
---
Restoration Settings
---
---
---
---
---
00
Number of Entries
04 hex
04 hex
---
USINT
RO
Not pos-
sible
---
01
Port 1 Restoration Setting
00 hex
00 or 01 hex
*1
*1. The meanings of the set values for the Restoration Settings are as follows:
---
USINT
RW
Not pos-
sible
Y
02
Port 2 Restoration Setting
00 hex
00 or 01 hex
*1
---
USINT
RW
Not pos-
sible
Y
03
Port 3 Restoration Setting
00 hex
00 or 01 hex
*1
---
USINT
RW
Not pos-
sible
Y
04
Port 4 Restoration Setting
00 hex
00 or 01 hex
*1
---
USINT
RW
Not pos-
sible
Y
Index
(hex)
Subindex
(hex)
Object name
Default
value
Data range
Unit
Data
type
Access
I/O allo-
cation
Data
attribute
5004
---
Load Rejection Output Settings ---
---
---
---
---
00
Number of Entries
04 hex
04 hex
---
USINT
RO
Not pos-
sible
---
01
Port 1 Load Rejection Output
Setting
00 hex
00 or 01 hex
*1
*1. The Load Rejection Output Settings are used to set the load rejection outputs to use when controller communications
errors occur. The meanings of the set values are as follows:
---
USINT
RW
Not pos-
sible
Y
02
Port 2 Load Rejection Output
Setting
00 hex
00 or 01 hex
*1
---
USINT
RW
Not pos-
sible
Y
03
Port 3 Load Rejection Output
Setting
00 hex
00 or 01 hex
*1
---
USINT
RW
Not pos-
sible
Y
04
Port 4 Load Rejection Output
Setting
00 hex
00 or 01 hex
*1
---
USINT
RW
Not pos-
sible
Y
Set value
Meaning
00 hex
Restoration is disabled.
01 hex
Restoration is enabled.
Set value
Meaning
00 hex
IO-Link Mode
Enabled: Output rejection notification is sent to the IO-Link device.
SIO (DO) Mode
Enabled: The output value is cleared to OFF.
01 hex
IO-Link Mode
Disabled: IO-Link communications continue with the last output data that was received.
SIO (DO) Mode
Disabled: The output that was last received is retained.
Summary of Contents for NX-ILM400
Page 12: ...Manual Structure 10 NX series IO Link Master Unit User s Manual W567...
Page 36: ...Revision History 34 NX series IO Link Master Unit User s Manual W567...
Page 38: ...Sections in this Manual 36 NX series IO Link Master Unit User s Manual W567...
Page 52: ...2 Specifications 2 4 NX series IO Link Master Unit User s Manual W567...
Page 58: ...3 Part Names and Functions 3 6 NX series IO Link Master Unit User s Manual W567...
Page 120: ...7 Troubleshooting 7 8 NX series IO Link Master Unit User s Manual W567...
Page 126: ...8 Inspection and Maintenance 8 6 NX series IO Link Master Unit User s Manual W567...