![Omron NX-ILM400 User Manual Download Page 138](http://html1.mh-extra.com/html/omron/nx-ilm400/nx-ilm400_user-manual_742779138.webp)
Appendices
A - 12
NX-series IO-Link Master Unit User’s Manual (W567)
These objects accept I/O allocations.
If you assign any of the objects that are described below to I/O, you can no longer access those objects
with the Read NX Unit Object instruction, Write NX Unit Object instruction, or other messages.
Objects That Accept I/O Allocations
Index
(hex)
Subindex
(hex)
Object name
Default
value
Data range
Unit
Data type
Access
I/O allo-
cation
Data
attri-
bute
6000
---
I/O Port Status
---
---
---
---
---
---
00
Number of Entries
1
1
---
USINT
RO
Not pos-
sible
---
01
I/O Port Status (Details pro-
vided later.
*1
)
0000
0000 to FFFF hex
---
WORD
RO
Possible
―
6001
---
Error Status for Ports 1 and 2
---
---
---
---
---
---
00
Number of Entries
1
1
---
USINT
RO
Not pos-
sible
---
01
Error Status for Ports 1 and 2
(Details provided later.
*2
)
0000
0000 to FFFF hex
---
WORD
RO
Possible
―
6002
---
Error Status for Ports 3 and 4
(Details provided later.
*3
)
---
---
---
---
---
---
00
Number of Entries
1
1
---
USINT
RO
Not pos-
sible
---
01
Error Status for Ports 3 and 4
0000
0000 to FFFF hex
---
WORD
RO
Possible
---
6003
---
Digital Input Data
---
---
---
---
---
---
00
Number of Entries
1
1
---
USINT
RO
Not pos-
sible
---
01
Digital Input Data (Details pro-
vided later.
*4
)
0000
0000 to FFFF hex
---
WORD
RO
Possible
---
6004
―
Port 1 Input Data
---
---
---
---
---
---
00
Number of Entries
10
00 to 10 hex
---
USINT
RO
Not pos-
sible
---
01
Port 1 Input Data 01
0000
0000 to FFFF hex
---
ARRAY
[0..1]
OF
BYTE
RO
Possible
---
02
Port 1 Input Data 02
0000
0000 to FFFF hex
---
ARRAY
[0..1]
OF
BYTE
RO
Possible
---
03
Port 1 Input Data 03
0000
0000 to FFFF hex
---
ARRAY
[0..1]
OF
BYTE
RO
Possible
---
04
Port 1 Input Data 04
0000
0000 to FFFF hex
---
ARRAY
[0..1]
OF
BYTE
RO
Possible
---
05
Port 1 Input Data 05
0000
0000 to FFFF hex
---
ARRAY
[0..1]
OF
BYTE
RO
Possible
---
06
Port 1 Input Data 06
0000
0000 to FFFF hex
---
ARRAY
[0..1]
OF
BYTE
RO
Possible
---
07
Port 1 Input Data 07
0000
0000 to FFFF hex
---
ARRAY
[0..1]
OF
BYTE
RO
Possible
---
Summary of Contents for NX-ILM400
Page 12: ...Manual Structure 10 NX series IO Link Master Unit User s Manual W567...
Page 36: ...Revision History 34 NX series IO Link Master Unit User s Manual W567...
Page 38: ...Sections in this Manual 36 NX series IO Link Master Unit User s Manual W567...
Page 52: ...2 Specifications 2 4 NX series IO Link Master Unit User s Manual W567...
Page 58: ...3 Part Names and Functions 3 6 NX series IO Link Master Unit User s Manual W567...
Page 120: ...7 Troubleshooting 7 8 NX series IO Link Master Unit User s Manual W567...
Page 126: ...8 Inspection and Maintenance 8 6 NX series IO Link Master Unit User s Manual W567...
Page 170: ...Appendices A 44 NX series IO Link Master Unit User s Manual W567...
Page 171: ...I 1 I NX series IO Link Master Unit User s Manual W567 Index...
Page 174: ...I 4 NX series IO Link Master Unit User s Manual W567 Index...
Page 175: ......