4 - 13
4 Installation and Wiring
NX-series IO-Link Master Unit User’s Manual (W567)
4-
3 W
irin
g
t
h
e T
ermin
als
4
4-
3-1 Wiring to the Screw
less Cla
m
ping T
er
m
inal Blo
ck
Dimensions of Wires Connected to the Terminal Block
The dimensions of wires that you can connect into the terminal holes of the screwless clamping ter-
minal block are as in the figure below.
Process the applicable wires that are specified in the following description to apply the dimensions.
Using Ferrules
If you use ferrules, attach the twisted wires to them.
Observe the application instructions for your ferrules for the wire stripping length when attaching fer-
rules.
Always use plated one-pin ferrules. Do not use unplated ferrules or two-pin ferrules.
The applicable ferrules, wires, and crimping tools are listed in the following table.
Terminal
types
Manufac-
turer
Ferrule
model
Applica-
ble wire
(mm
2
(AWG))
Crimping tool
Terminals
other than
ground ter-
minals
Phoenix
Contact
AI0,34-8
0.34 (#22)
Phoenix Contact (The figure in parentheses is the
applicable wire size.)
CRIMPFOX 6 (0.25 to 6 mm
2
, AWG24 to 10)
AI0,5-8
0.5 (#20)
AI0,5-10
AI0,75-8
0.75 (#18)
AI0,75-10
AI1,0-8
1.0 (#18)
AI1,0-10
AI1,5-8
1.5 (#16)
AI1,5-10
Ground ter-
minals
AI2,5-10
2.0
*1
*1. Some AWG14 wires exceed 2.0 mm
2
and cannot be used in the screwless clamping terminal block.
Terminals
other than
ground ter-
minals
Weidmuller
H0.14/12
0.14 (#26)
Weidmuller (The figure in parentheses is the appli-
cable wire size.)
PZ6 Roto (0.14 to 6 mm
2
, AWG26 to 10)
H0.25/12
0.25 (#24)
H0.34/12
0.34 (#22)
H0.5/14
0.5 (#20)
H0.5/16
H0.75/14
0.75 (#18)
H0.75/16
H1.0/14
1.0 (#18)
H1.0/16
H1.5/14
1.5 (#16)
H1.5/16
1.6 mm max. (Terminals other than ground terminals)
2.0 mm max. (Ground terminals)
2.4 mm max. (Terminals other than ground terminals)
2.7 mm max. (Ground terminals)
Summary of Contents for NX-ILM400
Page 12: ...Manual Structure 10 NX series IO Link Master Unit User s Manual W567...
Page 36: ...Revision History 34 NX series IO Link Master Unit User s Manual W567...
Page 38: ...Sections in this Manual 36 NX series IO Link Master Unit User s Manual W567...
Page 52: ...2 Specifications 2 4 NX series IO Link Master Unit User s Manual W567...
Page 58: ...3 Part Names and Functions 3 6 NX series IO Link Master Unit User s Manual W567...
Page 120: ...7 Troubleshooting 7 8 NX series IO Link Master Unit User s Manual W567...
Page 126: ...8 Inspection and Maintenance 8 6 NX series IO Link Master Unit User s Manual W567...
Page 170: ...Appendices A 44 NX series IO Link Master Unit User s Manual W567...
Page 171: ...I 1 I NX series IO Link Master Unit User s Manual W567 Index...
Page 174: ...I 4 NX series IO Link Master Unit User s Manual W567 Index...
Page 175: ......