3-1 Maximum I/O Response
T
ime When
the Ether
CA
T C
oupler Unit Is Connected
5-3
Communications Performance
This section describes the I/O response times of the IO-Link Master Unit.
The I/O response time is the time required for the following processing: The CPU Unit processes an
external signal input to one NX Unit, and another NX Unit outputs the processed result as an external
signal.
This section describes the maximum I/O response time of the IO-Link Master Unit when an EtherCAT
Coupler Unit is connected.
For information on timing charts and calculation methods for I/O response times for NX Units in Ether-
CAT Slave Terminals, refer to
Free-Run Refreshing I/O Response Times
in the
NX-series EtherCAT
Coupler Unit User's Manual
(Cat. No. W519).
The following NX Unit parameters are necessary to calculate I/O response times.
• Tnx-InProc: Input data processing time of the NX Unit
• Tnx-Indelay: Input delay time of the NX Unit
• Tnx-OutProc: Output data processing time of the NX Unit
• Tnx-Outdelay: Output delay time of the NX Unit
The parameter values and calculation methods for the IO-Link Master Unit are given below.
Input Data
5-3-1
Maximum I/O Response Time When the EtherCAT Coupler Unit Is
Connected
I/O data type
IO-Link process input data
from IO-Link communica-
tions in IO-Link Mode
Digital input data for pin 2
in IO-Link Mode
Digital input data in SIO
(DI) Mode
Parameter
Tnx-InProc
0[ms]
Tnx-Indelay
0.072 × (Total size (in bytes)
of IO-Link process input data
from IO-Link communica-
tions from port 1 to port 4) +
2.61+ IO-Link communica-
tions cycle
*1
[ms]
*1. For information on how to determine the IO-Link communications cycle, refer to
5-3-4 Determining the IO-Link
Communications Cycle
on page 5-11.
0.072 × (Total size (in bytes) of IO-Link process input data
from IO-Link communications from port 1 to port 4) + 2.61+
Input filter time [ms]
Example: When port 1
through port 4 are all used by
IO-Link devices (sensors) with
an IO-Link input data size of 2
bytes, and the IO-Link com-
munications cycle for those
IO-Link devices (sensors) is
2.1 [ms]: 0.072 × 2 bytes × 4
d 2.61 + 2.1 = 5.286
[ms]
Example: When port 1
through port 4 are all used
by IO-Link devices (sensors)
with an IO-Link input data
size of 2 bytes and no input
filter is used: 0.072 × 2 bytes
× 4 d 2.61 = 3.186
[ms]
Example: When port 1
through port 3 are used by
IO-Link devices with an
IO-Link input data size of 2
bytes and port 4 is used by a
non-IO-Link device with no
input filter: 0.072 × 2 bytes ×
3 d 2.61 = 3.042
[ms]
Summary of Contents for NX-ILM400
Page 12: ...Manual Structure 10 NX series IO Link Master Unit User s Manual W567...
Page 36: ...Revision History 34 NX series IO Link Master Unit User s Manual W567...
Page 38: ...Sections in this Manual 36 NX series IO Link Master Unit User s Manual W567...
Page 52: ...2 Specifications 2 4 NX series IO Link Master Unit User s Manual W567...
Page 58: ...3 Part Names and Functions 3 6 NX series IO Link Master Unit User s Manual W567...
Page 120: ...7 Troubleshooting 7 8 NX series IO Link Master Unit User s Manual W567...
Page 126: ...8 Inspection and Maintenance 8 6 NX series IO Link Master Unit User s Manual W567...
Page 170: ...Appendices A 44 NX series IO Link Master Unit User s Manual W567...
Page 171: ...I 1 I NX series IO Link Master Unit User s Manual W567 Index...
Page 174: ...I 4 NX series IO Link Master Unit User s Manual W567 Index...
Page 175: ......