![background image](http://html1.mh-extra.com/html/omron/nx-ilm400/nx-ilm400_user-manual_742779158.webp)
Appendices
A - 32
NX-series IO-Link Master Unit User’s Manual (W567)
*3. Indicates the state of the IO-Link master and the IO-Link device when a sent message is received. The meanings of the
values are as follows:
*4. Specifies the index number of the object in the IO-Link device.
*5. Specifies the subindex number of the object in the IO-Link device.
*6. Specifies the size of the data to be written during writing.
*7. Specifies the data to be written during writing.
*8. The default value of all data in 232 bytes is 00 hex.
*9. The setting range of all data in 232 bytes is 00 to FF hex.
*10.Indicates the error codes for the case when the value of the status of subindex 02 hex is either 04 hex or 05 hex. The
meanings of the error codes are as follows. When the value of status is 02 hex, the meaning is normal end, and value of
error code is 0000 hex.
*11.This is the time required for the IO-Link master to monitor the response from the IO-Link device. If 0000 hex is specified,
monitoring is performed in 2 s.
*12.Specifies the sequence number of the message to be sent.
Index
(hex)
Subindex
(hex)
Object name
Default
value
Data range
Unit
Data
type
Access
I/O allo-
cation
Data
attribute
5018
---
Clear Backup Data Command
---
---
---
---
---
00
Number of Entries
01 hex
01 hex
---
USINT
RO
Not pos-
sible
---
01
Command
00 hex
00 or 01 hex
*1
---
USINT
RW
Not pos-
sible
N
02
Result
*2
0000, 0001, and
FFFF hex
*2
UINT
RO
Not pos-
sible
N
Value
Meaning
00 hex
No operation
01 hex
Busy
02 hex
Successful
03 hex
Reserved
04 hex
Error (IO-Link Master)
05 hex
Error (IO-Link Device)
Value of
status
Value of error
code
Meaning of error code
Correction
04 hex
4806 hex
The communications mode of the
port is not set to IO-Link Mode.
Set the communications mode of the port to
IO-Link Mode.
4807 hex
There is no IO-Link device.
Connect an IO-Link device.
The I/O power supply has been
turned OFF.
Turn ON the I/O power supply.
Timeout has occurred.
Change the timeout setting.
An IO-Link Communications Module
Processing Error (event code:
849A0000 hex) occurs.
Refer to the Sysmac event codes and
implement countermeasures. Refer to the
IO-Link System User’s Manual
(Cat. No.
W570) for details on the Sysmac event
codes.
4808 hex
An IO-Link Communications Error
(event code: 848D0000 hex) occurs.
A Device Configuration Verification
Error (event code: 848F0000 hex)
occurs.
05 hex
• Upper 1 byte
Error code
defined in the
IO-Link standard
• Lower 1 byte
Additional code
defined in the
IO-Link standard
Refer to Table C.1 Error Types in
Annex C of the IO-Link Interface
and System Specification Version
1.1.2 for details on the meanings of
the error codes.
Refer to the handling instructions for the
IO-Link device that is connected to and
implement countermeasures.
Summary of Contents for NX-ILM400
Page 12: ...Manual Structure 10 NX series IO Link Master Unit User s Manual W567...
Page 36: ...Revision History 34 NX series IO Link Master Unit User s Manual W567...
Page 38: ...Sections in this Manual 36 NX series IO Link Master Unit User s Manual W567...
Page 52: ...2 Specifications 2 4 NX series IO Link Master Unit User s Manual W567...
Page 58: ...3 Part Names and Functions 3 6 NX series IO Link Master Unit User s Manual W567...
Page 120: ...7 Troubleshooting 7 8 NX series IO Link Master Unit User s Manual W567...
Page 126: ...8 Inspection and Maintenance 8 6 NX series IO Link Master Unit User s Manual W567...
Page 170: ...Appendices A 44 NX series IO Link Master Unit User s Manual W567...
Page 171: ...I 1 I NX series IO Link Master Unit User s Manual W567 Index...
Page 174: ...I 4 NX series IO Link Master Unit User s Manual W567 Index...
Page 175: ......