- 15 -
(ii)F3SH
3.Auxiliary output
9.Initialize
0.ID
7.Restart interlock
6.Start interlock
3.AUX
4.E.I.O.
4.Ext. indicator output
5.Ext. device monitor
5.EDM
6.SIL
7.RIL
9.INI
0.ID
A.Threshold teach
A.TCH
B.Error log view
B.LOG
(iii)F3ZN
1.Fixed blanking
3.Output #2
8.Threshold
2.Floating blanking
4.Ext. indicator output
9.Initialized
0.ID
9.INI
0.ID
1.FIX
2.FLO
3.OU2
4.E.I.O.
8.TH
B.Error log view
0.LOG
<Common Note for MONITOR/SET function>
1. Edited value will not become active if NOT “SEND” to sensor, nor
“Function Valid (1.Fun-on)” is not selected.
2. “Loc” may display if “Setting lock” or “Setting limitation” has been
set. See clause10.1 and 10.3.
3. Please do not drop a power supply on the "Send" display after
pushing the [ENTER] key before being displayed as "Good." When
a power supply should be dropped, a sensor may not carry out
normal operation.
- 16 -
8.1 Fixed
blanking
<F3SN, F3ZN>
CAUTION
In order prevent access to a dangerous area, fixed barrier guards
must be placed in fixed blanked areas.
Failure to do so may result in serious injury.
When Floating blanking function is enabled simultaneously, the
beam more than a plan may become invalid.
Please perform sufficient verification, when you confirm both
functions simultaneously.
Failure to do so may result in serious injury.
Fixed blanking function partly voids detection zone of sensor. Entrance
of object into invalid detection zone does not change output status.
There are two ways to choose which zone is to be blanked.
1. Teaching: Blocked beams are set as beams for blanking. Error will
be displayed if there are no blocked beams.
2.
Manual: Select beam number first, and then choose
blanked/not blanked for each selected beam. Beams are
numbered as below figure.
7
6
5
4
3
2
1