![background image](http://html.mh-extra.com/html/omron/cp1e-e-d-series/cp1e-e-d-series_user-manual_742511211.webp)
8-43
8 Using Expansion Units and Expansion I/O Units
CP1E CPU Unit Hardware User’s Manual(W479)
8-3 An
alog
I/O U
n
its
8
8-3
-2 C
P
1W-
M
AD42/CP1W-
M
A
D
44 Analog I/O
Units
Analog Input Signal Ranges
−
10 to 10 V
The
−
10 to 10 V range corresponds to the hexadecimal values E890 to 1770 (
−
6000 to 6000). The
entire data range is E638 to 19C8 (
−
6600 to 6600).
A negative voltage is expressed as a two’s complement.
0 to 10 V
The 0 to 10 V range corresponds to the hexadecimal values 0000 to 2EE0 (0 to 12000). The entire
data range is FDA8 to 3138 (
−
600 to 12600). A negative voltage is expressed as a two’s comple-
ment.
0 to 5 V
The 0 to 5 V range corresponds to the hexadecimal values 0000 to 2EE0 (0 to 12000). The entire
data range is FDA8 to 3138 (
−
600 to 12600). A negative voltage is expressed as a two’s comple-
ment.
0 V
10 V 11 V
−
11V
−
10V
E890 (
−
6000)
E638 (
−
6600)
19C8 (6600)
1770 (6000)
0000 (0)
Converted Data
Hexadecimal (Decimal)
0 V
10 V 10.5 V
−
0.5 V
FDA8 (
−
600)
3138 (12600)
2EE0 (12000)
0000 (0)
Converted Data
Hexadecimal (Decimal)
0 V
5 V 5.25 V
−
0.25 V
FDA8 (
−
600)
3138 (12600)
2EE0 (12000)
0000 (0)
Converted Data
Hexadecimal (Decimal)
Summary of Contents for CP1E-E**D Series
Page 3: ......
Page 66: ...2 Basic System Configuration and Devices 2 22 CP1E CPU Unit Hardware User s Manual W479...
Page 318: ...Appendices A 54 CP1E CPU Unit Hardware User s Manual W479...
Page 322: ...Index 4 CP1E CPU Unit Hardware User s Manual W479...
Page 324: ...Revision 2 CP1E CPU Unit Hardware User s Manual W479...
Page 325: ......