![background image](http://html.mh-extra.com/html/omron/cp1e-e-d-series/cp1e-e-d-series_user-manual_742511195.webp)
8-27
8 Using Expansion Units and Expansion I/O Units
CP1E CPU Unit Hardware User’s Manual(W479)
8-3 An
alog
I/O U
n
its
8
8-3
-1 CP1W-MAD
11 Analo
g I/O Unit
s
8-3
Analog I/O Units
Each CP1W-MAD11 Analog I/O Unit provides 2 analog inputs and 1 analog output.
•
The analog input range can be set to 0 to 5 V, 1 to 5 V, 0 to 10 V, -10 to 10 V, 0 to 20 mA, or 4 to 20
mA. The inputs have a resolution of 1/6000. An open-circuit detection function is activated in the
ranges of 1 to 5 V and 4 to 20 mA.
•
The analog output range can be set to 1 to 5 V, 0 to 10 V, -10 to 10 V, 0 to 20 mA, or 4 to 20 mA. The
outputs have a resolution of 1/6000.
CP1W-MAD11
(1)Analog I/O Terminals
Connected to analog I/O devices.
•
I/O Terminal Arrangements
Note
For current inputs, short V IN0 to I IN0 and V IN1 to I IN1.
(2)Expansion I/O Connecting Cable
Connected to the expansion connector of a CPU Unit or an Expansion Unit or Expansion I/O Unit.
The cable is provided with the Analog I/O Unit and cannot be removed.
8-3-1
CP1W-MAD11 Analog I/O Units
Overview
Part Names and Functions
V OUT
Voltage output
I OUT
Current output
COM
Output common
V IN0
Voltage input 0
I IN0
Current input 0
COM0
Input common 0
V IN1
Voltage input 1
I IN1
Current input 1
COM1
Input common 1
NC
NC
(3) Expansion connector
(2) Expansion I/O connecting cable
(1) Analog I/O terminals
(4) DIP switch
I OUT
V IN0 COM0
V OUT COM
I IN0
I IN1
V IN1 COM1
N C
N C
A G
N C
N C
Summary of Contents for CP1E-E**D Series
Page 3: ......
Page 66: ...2 Basic System Configuration and Devices 2 22 CP1E CPU Unit Hardware User s Manual W479...
Page 318: ...Appendices A 54 CP1E CPU Unit Hardware User s Manual W479...
Page 322: ...Index 4 CP1E CPU Unit Hardware User s Manual W479...
Page 324: ...Revision 2 CP1E CPU Unit Hardware User s Manual W479...