8-83
8 Using Expansion Units and Expansion I/O Units
CP1E CPU Unit Hardware User’s Manual(W479)
8-4 T
e
mp
eratu
re
S
e
nsor U
n
its
8
8-4
-3 T
S
0
04 Temper
ature
S
e
nsor
Units
2
Set temperature ranges.
Precautions for Safe Use
Do not touch the DIP switch while power is being supplied. Static electricity may cause operating
errors.
Precautions for Correct Use
Precautions for Correct Use
Always turn OFF the power supply before setting the temperature range.
With the Temperature Sensor Unit’s DIP switch, set the temperature unit and the temperature
input range.
Additional Information
Fahrenheit temperature uses the following equation to convert the temperature unit from Cel-
sius, but the temperature input range is different between Fahrenheit and Celsius.
Fahrenheit temperature (°F) = Celsius temperature (°C)
×
1.8 + 32
Set the temperature range according to the type of temperature sensor
connected to the Unit.
Temperature data will not be converted correctly if the temperature range
does not match the sensor.
Do not set the temperature range to any values other than those for
which temperature ranges are given in the following table.
An incorrect setting may cause operating errors.
SW
Setting
1
Input type
ON
J
OFF
K
2
Temperature unit
ON
°F
OFF
°C
Temperature input
Input type
Range (°C)
Range (°F)
K
-200.0 to 1300.0
-300.0 to 2300.0
J
-100.0 to 850.0
-100.0 to 1500.0
Caution
SW1
ON
OFF
SW2
Summary of Contents for CP1E-E**D Series
Page 3: ......
Page 66: ...2 Basic System Configuration and Devices 2 22 CP1E CPU Unit Hardware User s Manual W479...
Page 318: ...Appendices A 54 CP1E CPU Unit Hardware User s Manual W479...
Page 322: ...Index 4 CP1E CPU Unit Hardware User s Manual W479...
Page 324: ...Revision 2 CP1E CPU Unit Hardware User s Manual W479...
Page 325: ......