8 Using Expansion Units and Expansion I/O Units
8-96
CP1E CPU Unit Hardware User’s Manual(W479)
Additional Information
•
Unused bits in the CompoBus/S I/O Link Unit’s output words can be used as work bits.
•
Unused bits in input word cannot be used as work bits.
(1) Determining Node Number
•
The CompoBus/S I/O Link Unit is a Slave Unit with 8 input bits and 8 output bits. The
node number setting is made using the DIP switch; the inputs and outputs share the
same node number.
•
The range of possible node number settings is determined by the type of PLC the Mas-
ter Unit is mounted to and the settings on the Master Unit.
For details, refer to the CompoBus/S Operation Manual (Cat. No. W266).
(2) Making DIP Switch Settings
Use the DIP switch to set the CompoBus/S I/O Link Unit’s node number, communications
mode, and the status of output data when a communications error occurs.
Precautions for Correct Use
Precautions for Correct Use
Always turn OFF the power supply before changing the DIP switch settings.
2
Determine the node number and make DIP switch settings.
3
Wire the CompoBus/S communications path.
BD L
BD H
Connect the CompoBus/S Communications Cable.
BD L
BD H NC (BS+)
NC
NC (BS
−
)
These terminals are not used. They can
however be used as communications power
supply relay terminals.
Summary of Contents for CP1E-E**D Series
Page 3: ......
Page 66: ...2 Basic System Configuration and Devices 2 22 CP1E CPU Unit Hardware User s Manual W479...
Page 318: ...Appendices A 54 CP1E CPU Unit Hardware User s Manual W479...
Page 322: ...Index 4 CP1E CPU Unit Hardware User s Manual W479...
Page 324: ...Revision 2 CP1E CPU Unit Hardware User s Manual W479...
Page 325: ......