Example: Scaling analog output values
Convert a value between 200 and 500 in D300 into 2 to 5 V to output the voltage from the analog
output word (CIO 102) of CP1W-DA042.
Data memory settings
Ladder program
Refer to 8-1 Example: Scaling analog input values for the descriptions of APR instruction.
Setting
Address
Data
Control word
D110
#0800
Unscaled minimum value (200)
D111
&200
Scaled minimum value (3,000)
D112
&3,000
Unscaled maximum value (500)
D113
&500
Scaled maximum value (12,000)
D114
&12,000
12,000
(5V)
3,000
(2V)
500
200
Value output to Analog Output Unit
(Scaled: 3,000 to 12,000)
Unscaled
data
(200 to
500)
(Data in CIO102)
(D300)
㩷
Always ON Flag
P_On
APR(069)
Use APR instruction for scaling.
D110
102
D300