8 Using Expansion Units and Expansion I/O Units
8-76
CP1E CPU Unit Hardware User’s Manual(W479)
With the Temperature Sensor Unit’s DIP switch, set the input type (temperature or analog
input), the input thermocouple type (K or J) and the temperature unit (°C or °F).
Additional Information
Fahrenheit temperature uses the following equation to convert the temperature unit from Cel-
sius, but the temperature input range is different between Fahrenheit and Celsius.
Fahrenheit temperature (°F) = Celsius temperature (°C) x 1.8 + 32
3
Connect Temperature Sensors.
(1) Thermocouples
Either K or J thermocouples can be connected, but all four thermocouples must be the
same type and the same input range. Only last two channels can be used as analog inputs.
SW
Setting
1
Thermocouple type of
temperature sensor
ON
J
OFF
K
2
Temperature unit
ON
°F
OFF
°C
3
NC
4
Input type selection for
the third input (Input 2)
ON
Analog input
OFF
Thermocouple
5
Input type selection for
the fourth input (Input 3)
ON
Analog input
OFF
Thermocouple
6
Analog input signal
range
ON
1 to 5V/4 to 20mA
OFF
0 to 10V
Temperature input
Analog input
Input type
Range (°C)
Range (°F)
Input type
Range
K
-200.0 to 1300.0
-300.0 to 2300.0
Voltage
0 to 10V/1 to 5V
J
-100.0 to 850.0
-100.0 to 1500.0
Current
4 to 20mA
SW 1
2
3
4
5
6
ON
OFF
Temperature input 0
LOOP0
−
LOOP0+
NC
LOOP1
−
LOOP1+
NC
I IN2
I IN3
Temperature input 1
Temperature input 2
Temperature input 3
LOOP2+
V IN2
LOOP3+
V IN3
LOOP2
−
COM2
LOOP3
−
COM3
Cold junction
compensator
Summary of Contents for CP1E-E**D Series
Page 3: ......
Page 66: ...2 Basic System Configuration and Devices 2 22 CP1E CPU Unit Hardware User s Manual W479...
Page 318: ...Appendices A 54 CP1E CPU Unit Hardware User s Manual W479...
Page 322: ...Index 4 CP1E CPU Unit Hardware User s Manual W479...
Page 324: ...Revision 2 CP1E CPU Unit Hardware User s Manual W479...
Page 325: ......