8 Using Expansion Units and Expansion I/O Units
CP1E CPU Unit Hardware User’s Manual(W479)
8-4 T
e
mp
eratu
re
S
e
nsor U
n
its
8
8-4
-2 CP1W-T
S003 Tempe
ratur
e S
e
nsor
Units
Analog Input Signal Ranges
Analog input data is digitally converted according to the input signal range as shown below.
Additional Information
When the input exceeds the specified range, the A/D conversion data will be fixed at either the
lower limit or upper limit.
0 to 10 V
The 0 to 10 V range corresponds to the hexadecimal values 0000 to 2EE0 (0 to 12000). The entire
data range is FDA8 to 3138 (
−
600 to 12600). A negative voltage is expressed as a two’s comple-
ment.
1 to 5 V
The 1 to 5 V range corresponds to the hexadecimal values 0000 to 2EE0 (0 to 12000). The entire
data range is FDA8 to 3138 (
−
600 to 12600). Inputs between 0.8 and 1 V are expressed as two’s
complements. If the input falls below 0.8 V, open-circuit detection will activate and converted data
will be 8000.
0 V
10 V 10.5 V
−
0.5 V
FDA8 (
−
600)
3138 (12600)
2EE0 (12000)
0000 (0)
Converted Data
Hexadecimal (Decimal)
1 V
5 V 5.2 V
0.8 V
FDA8 (
−
600)
3138 (12600)
2EE0 (12000)
0000 (0)
Converted Data
Hexadecimal (Decimal)
Summary of Contents for CP1E-E**D Series
Page 3: ......
Page 66: ...2 Basic System Configuration and Devices 2 22 CP1E CPU Unit Hardware User s Manual W479...
Page 318: ...Appendices A 54 CP1E CPU Unit Hardware User s Manual W479...
Page 322: ...Index 4 CP1E CPU Unit Hardware User s Manual W479...
Page 324: ...Revision 2 CP1E CPU Unit Hardware User s Manual W479...
Page 325: ......