(4) Programming Example
The temperature data of CP1W-TS004 (12 inputs, input type is J type and temperature unit
is °C) is stored in D0 to D11.
When it occurs open-circuit alarm, W10.00 to W10.11 is ON.
•
Temperature Data Storage Address
Input word
Read command
CIO n+1
Temperature data
storage address
Open-circuit alarm
Input 0
#9901
D0
W0.00
Input 1
#9902
D1
W0.01
Input 2
#9903
D2
W0.02
Input 3
#9904
D3
W0.03
Input 4
#9905
D4
W0.04
Input 5
#9906
D5
W0.05
Input 6
#9907
D6
W0.06
Input 7
#9908
D7
W0.07
Input 8
#9909
D8
W0.08
Input 9
#990A
D9
W0.09
Input 10
#990B
D10
W0.10
Input 11
#990C
D11
W0.11
CIO 102
CP1E
Input word
addresses
Input range
J: SW1 OFF
Temperature unit
˚C: SW2 ON
Output word
addresses
CIO 0
CIO 1
CIO 100
CIO 101
CIO 2
CIO 3
CP1W-TS004
Temperature Sensor Unit
Summary of Contents for CP1E-E**D Series
Page 3: ......
Page 66: ...2 Basic System Configuration and Devices 2 22 CP1E CPU Unit Hardware User s Manual W479...
Page 318: ...Appendices A 54 CP1E CPU Unit Hardware User s Manual W479...
Page 322: ...Index 4 CP1E CPU Unit Hardware User s Manual W479...
Page 324: ...Revision 2 CP1E CPU Unit Hardware User s Manual W479...
Page 325: ......